Overcurrent protection adjustment when connecting synchronous generation to power supply systems / Samoylenko Vladislav O.,Korkunova Olga L.,Pazderin Andrew V.,Novikov Nicolas N. // . - 2015. - V. , l. . - P. 2368-2373.

ISSN/EISSN:
нет данных / нет данных
Type:
Proceedings Paper
Abstract:
The paper is devoted to the features of short-circuit current interruption under the conditions of small-scale distributed synchronous generation connection to medium voltage (MV) and low voltage (LV) power supply systems. Distributed generation (DG) even in a case of the unidirectional power supply has a great impact on overcurrent relay protection sensitivity and selectivity. Connecting DG leads to the specific character of short-circuit currents (SSC) of power supply systems, including increased level of short-circuit currents, current attenuation and the rate of aperiodic and periodic components. The paper also considers selection of setting values of specified time depending upon switchgear performance and the possibility of relay protection coordination for a generator and adjacent grid components.
Author keywords:
microgrids; distributed generation; relay protection; short-circuit; power supply; switchgear
DOI:
нет данных
Web of Science ID:
ISI:000377572202044
Соавторы в МНС:
Другие поля
Поле Значение
Book-Group-Author IEEE
Booktitle 2015 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY (ICIT)
Note IEEE International Conference on Industrial Technology (ICIT), Seville, SPAIN, MAR 17-19, 2015
Organization IEEE
Publisher IEEE
Address 345 E 47TH ST, NEW YORK, NY 10017 USA
Language English
ISBN 978-1-4799-7800-7
Research-Areas Engineering
Web-of-Science-Categories Engineering, Industrial; Engineering, Electrical \& Electronic
Author-Email vvsamoylenko@yandex.ru novikovustu@mail.ru
ResearcherID-Numbers Samoylenko, Vladislav/M-7436-2013 Pazderin, Andrey/M-7752-2016
ORCID-Numbers Pazderin, Andrey/0000-0003-4826-2387
Number-of-Cited-References 17
Doc-Delivery-Number BE9HU